In a house, water usually arrives through pipes of 16 to 20 mm outside diameter (25 or 26 mm for the main supply of a large villa), and leaves through 32 to 40 mm PVC pipes for washbasins, showers and sinks, and 100 mm pipes for WCs and soil stacks. These figures are practical benchmarks, derived from the calculation rules of DTU 60.11, the French reference that most Moroccan specifications adopt.
Supply: minimum diameters per fixture
DTU 60.11 sets, for each fixture, a base flow rate and a minimum inside diameter for the pipe that feeds it. The values below are those commonly quoted in professional guides; they should be checked against the edition being applied.
| Fixture | Minimum inside diameter | In practice (multilayer or PEX) |
|---|---|---|
| Washbasin, bidet, cistern WC | 10 mm | 16 mm pipe |
| Shower, kitchen sink | 12 mm | 16 mm pipe |
| Bathtub | 13 mm | 16 or 20 mm pipe |
| Washing machine, dishwasher | 10 mm | 16 mm pipe |
| Main supply, manifold inlet, water heater | based on the simultaneous flow calculation | 20 to 26 mm |
Watch the terminology: a "16" pipe often refers to the outside diameter. Depending on the wall thickness, the inside bore is about 12 to 13 mm, which is enough for one fixture but not to supply an entire bathroom.
Drainage: the usual PVC sizes
- Washbasin, bidet: 32 mm PVC (40 mm if the run is long).
- Shower, bathtub, kitchen sink, washing machine, dishwasher: 40 mm PVC, often 50 mm for a branch that collects several fixtures.
- WC: 100 mm PVC (DTU 60.11 sets a minimum inside diameter of around 80 mm).
- Vertical soil stack receiving WCs: 100 mm, extended through the roof for ventilation (see primary ventilation).
- Buried drain to the inspection chamber or sewer: 100 to 125 mm for a villa, larger for an apartment building.
Diameter is not enough: a drain without sufficient slope will clog even if it is correctly sized. The slope rules are detailed in our article on the slope of wastewater drains.
Why you do not simply choose "the biggest"
Oversizing the supply brings no benefit: water stagnates more, hot water takes longer to arrive, and the cost goes up. Conversely, a network that is too narrow loses pressure as soon as two fixtures run at the same time. The right diameter comes from a simple calculation: you add up the base flow rates of the fixtures, apply a simultaneity factor (not all taps are open at the same time), then check the water velocity, staying at around 1.5 to 2 m/s maximum to limit noise.
Common situations in Morocco
In a villa with a roof terrace, a solar water heater and a rooftop tank, water sometimes arrives by gravity with very little pressure: larger diameters or a booster pump are then needed. In riads, the long distances between the meter and the bathrooms also require the pipe sizes to be recalculated.
The role of the engineering firm
For a villa with several bathrooms, an apartment building or a guesthouse, the engineering firm prepares the calculation note (flow rates, simultaneity, pressure losses), the supply and drainage drawings and the pipe size schedule. This file makes it possible to compare quotes on an identical basis and to avoid surprises when the system is filled.
Frequently asked questions
What pipe diameter should be used to supply a house?
In practice, each fixture is supplied with a 16 mm pipe, and 20 to 26 mm is provided for the main supply and the manifold inlet, depending on the number of outlets used at the same time.
What diameter for a WC drain?
A WC drains through 100 mm PVC; DTU 60.11 sets a minimum inside diameter of around 80 mm for this fixture.
What diameter for a shower drain?
40 mm PVC is commonly used for a shower, and 50 mm when the pipe also collects other fixtures or when the run is long.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : CAPEB, calepin plomberie · La Maison Saint-Gobain, choisir les tuyaux de plomberie · AFNOR, NF DTU 60.11.