Natural or mechanical smoke control: principle, choice and upkeep

In a fire, smoke is the biggest killer. Smoke control keeps staircases and corridors usable for the time it takes to evacuate.

Published 16 November 2026 · 5 min read · SIGMA ICC, engineering consultancy

Smoke control serves to remove the smoke and hot gases from a fire in order to keep escape routes visible and breathable and to make the emergency services' work easier. It can be natural, by thermal draught through high-level openings and low-level air inlets, or mechanical, with fans. The fire safety regulation (Decree 2-14-499) states which rooms must have smoke control and under which rules.

The two principles

CriterionNaturalMechanical
OperationHot smoke rises and leaves through smoke vents or high windows; fresh air enters low downExtraction fans and, often, supply fans in ducts
EnergyNone needed to operate (control only)Backed-up power supply essential
ConstraintsNeeds available facades or roofs; sensitive to windDucts, plant rooms, fans resistant to hot smoke
Typical casesStaircases, small shops, halls with an accessible roofUnderground rooms, windowless corridors, car parks, large volumes
CostLowerHigher, heavier maintenance

The sizing rules to know

  • Effective area: in natural smoke control, the area of the outlets is proportional to the area of the room. As a benchmark, French ERP regulations often use an effective area of about 1/200 of the room's floor area.
  • Air inlets: without fresh air entering low down, the smoke does not leave. Their area must be at least comparable to that of the outlets.
  • Smoke zoning: large volumes are divided into smoke zones by curtains to prevent the smoke from spreading.
  • Mechanical flow rates: they are calculated according to the volume or area to be cleared and the type of room; this is an engineering calculation, not a flat figure.

The exact values to apply are those of the Moroccan regulation and its technical instructions; the benchmarks above only give orders of magnitude.

Control and safety actions

Smoke control is triggered manually (control near the access, usable by the emergency services) or automatically by fire detection. In a building equipped with a fire safety system, it is the control panel that opens the dampers and smoke vents, stops the comfort ventilation and starts the smoke extraction fans. The air conditioning must imperatively stop: otherwise, it spreads the smoke throughout the building.

Maintenance

  1. Periodic opening test of the smoke vents and dampers, and start-up test of the fans.
  2. Checking the air inlets: they must not be blocked by furniture or added partitions.
  3. Checking the safety power supplies.

In riads, covering a patio with a fixed glass roof often eliminates the natural draught: this should be studied before the works.

The role of the engineering firm

The engineering firm identifies the rooms requiring smoke control, chooses the principle, calculates areas and flow rates, sizes the ducts and fans and organises the interlocks. For car parks, see our article on car park smoke control.

Frequently asked questions

What is the difference between natural and mechanical smoke control?

Natural smoke control removes smoke by thermal draught through high openings, with air inlets low down; mechanical smoke control uses fans and ducts and requires a backed-up power supply.

What opening area for natural smoke control?

It is proportional to the room's area; for ERP, French regulations often use about 1/200 of the floor area, to be checked against the applicable Moroccan regulation.

Why switch off the air conditioning in a fire?

Because the comfort ventilation would spread the smoke throughout the building; the fire control panel stops it automatically during the safety actions.

A project in the pipeline?

SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.

Sources : Kingspan, réglementation désenfumage ERP · France Air, guide du désenfumage en ERP.