Home / Advice / Electrical / Kitchen electrics

Kitchen electrics: sockets, circuits and heights by the standard

The kitchen is the room with the heaviest electrical load in a house. Here is the number of sockets, the circuits to plan and the locations to avoid, based on the NF C 15-100 benchmarks.

Published 16 November 2026 · 4 min read · SIGMA ICC, engineering consultancy

According to the NF C 15-100 benchmarks, a kitchen larger than 4 m² has at least 6 sockets, including 4 above the worktop, supplied by a dedicated 2.5 mm² circuit. Large appliances (oven, hob, dishwasher, washing machine if it is in the kitchen) each have their own dedicated circuit, which does not count towards these 6 sockets. No socket is installed above the sink or the hob.

In Morocco, the NM 06.1.100 to 06.1.106 series of standards governs low-voltage installations, and design office specifications still refer very widely to NF C 15-100. The figures below are the most commonly applied rules; the 2024 edition of the French standard has changed some of the wording.

How many sockets and circuits in a kitchen?

UseUsual benchmarkCircuit
General-purpose sockets (kitchen over 4 m²)6 minimum, including 4 above the worktopDedicated 2.5 mm² circuit, 20 A protection
General-purpose sockets (kitchen of 4 m² or less)3 minimumDedicated 2.5 mm² circuit, 20 A protection
Single-phase hob1 cable outlet or box6 mm², 32 A protection
Oven1 dedicated socket2.5 mm², 20 A protection
Dishwasher1 dedicated socket2.5 mm², 20 A protection
Cooker hood1 socket or cable outlet, high upMay be taken from another circuit depending on its power

The fridge, microwave or coffee machine plug into the general-purpose sockets. In a villa, people often plan more than the minimum: a central island, a back kitchen or a freezer in the pantry justify extra sockets, or even a second circuit so as not to exceed the number of sockets allowed per circuit (see how many sockets per circuit).

Where to place sockets and at what height?

  • Above the worktop: sockets are installed a few centimetres above the splashback (guides generally quote at least 5 to 8 cm above the worktop), to avoid splashes and make cleaning easier.
  • Never above the sink or the hob: a cable hanging over a burner or a water point is a fire and electrocution risk. Professionals advise keeping a gap of about 60 cm between a socket and the sink, as good practice.
  • Cooker hood: its socket or cable outlet is placed high up, at the level of the hood, and labelled.
  • Built-in appliances: the dishwasher and oven sockets are placed in an adjacent cabinet or in an accessible lower section, not behind the appliance if it can no longer be moved.

RCD protection and earthing

All kitchen circuits go through a 30 mA residual current device. Appliances with electronics (induction hob, recent dishwashers) are usually placed under a type A RCD rather than type AC. All sockets have an earth pin, connected to a good-quality earth electrode. In a restaurant kitchen or a riad converted into a guesthouse, power levels change scale (combi ovens, three-phase hobs, cold rooms) and a specific power assessment is required.

Common mistakes on site

  • Connecting the oven and the hob to the same line or to an ordinary 16 A socket.
  • Underestimating the induction hob: it needs a 6 mm² line and a 32 A rating in single-phase.
  • Forgetting the central island sockets, which must be fed through the floor before the screed is poured.
  • Installing the sockets before the kitchen designer's plan is known: they end up behind a tall unit or above the sink.

The role of the design office

The design office cross-checks the kitchen designer's plan with the wiring diagram: it sets the number of circuits, the cable sizes and the protective devices, and checks that the kitchen's power fits within the overall assessment for the house. This is also the time to plan floor reservations for an island. For the other mandatory circuits in the house, see dedicated circuits and wiring the oven and hob.

Frequently asked questions

How many sockets are needed in a kitchen?

According to the NF C 15-100 benchmarks, at least 6 sockets in a kitchen larger than 4 m², including 4 above the worktop, not counting the dedicated sockets for large appliances.

Can a socket be placed above the sink?

No: no socket may be installed above the sink or the hob. Only the cooker hood has a socket or cable outlet high up.

What cable for a hob?

A single-phase hob is supplied by a dedicated 6 mm² copper circuit, protected by a 32 A circuit breaker.

A project in the pipeline?

SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.

Sources : Legrand, la norme NF C 15-100 pour la cuisine · IZI by EDF, que dit la norme pour une cuisine · Selectra, prises obligatoires NF C 15-100.