In single-phase, the hob (or cooker) is supplied by a dedicated 6 mm² circuit protected by a 32 A circuit breaker, placed downstream of a 30 mA type A residual current switch. The oven also has its own circuit, commonly 2.5 mm² protected by a 20 A circuit breaker. In three-phase, the hob can be supplied in 2.5 mm² with a 20 A four-pole circuit breaker. These are the NF C 15-100 benchmarks, the reference most used by engineering firms in Morocco.
The usual values
| Appliance | Supply | Cable cross-section | Circuit breaker |
|---|---|---|---|
| Hob or cooker | Single-phase 230 V | 6 mm² | 32 A |
| Hob | Three-phase 400 V | 2.5 mm² (5 conductors) | 20 A |
| Built-in oven | Single-phase 230 V | 2.5 mm² | 20 A |
| Hood, microwave, small appliances | Single-phase 230 V | Kitchen socket circuit 2.5 mm² | 20 A |
Some hob manufacturers or certain manuals specify other ratings for three-phase or two-phase connection: the appliance manual and the engineering firm's calculation note take precedence over generic tables.
Connection: cable outlet or socket
- Hob: connection via a connection box (cable outlet) or a dedicated 32 A socket, placed so that it remains accessible under the worktop.
- Oven: dedicated 16 A or 20 A socket, or cable outlet depending on the model. A socket placed behind the oven must be possible to disconnect by pulling the appliance out.
- Residual current device: the hob circuit must be under a 30 mA type A residual current switch, because induction hobs generate leakage currents that type AC does not detect correctly.
Mistakes to avoid
- Plugging the hob into a 16 A socket with an extension lead or adapter: risk of overheating and fire.
- Putting the oven and the hob on the same 32 A circuit: each appliance must have its own circuit, except an all-in-one cooker.
- Undersizing a long cable: if the kitchen is far from the board (single-storey villa, summer kitchen near the pool), voltage drop may require a larger cross-section.
- Forgetting three-phase: in a villa with a three-phase connection, supplying the hob in three-phase spreads the load better between the phases.
The engineering firm's view
In a villa or a high-end apartment, the kitchen may include an induction hob, two ovens, a dishwasher, an American-style refrigerator and a wine cooler. The engineering firm includes these loads in the electrical power balance, chooses the cross-sections, distributes the circuits between the residual current devices and checks the power to be contracted with the distributor. See also mandatory dedicated circuits and the cable cross-section / rating table.
Frequently asked questions
What cable size for an induction hob?
In single-phase, the hob is supplied in 6 mm² with a 32 A circuit breaker, under a 30 mA type A residual current device; in three-phase, 2.5 mm² with a 20 A circuit breaker is the usual value.
Which circuit breaker for an electric oven?
The oven has a dedicated circuit, commonly 2.5 mm² protected by a 20 A circuit breaker, unless the manufacturer's manual states otherwise.
Can the oven and hob be on the same circuit breaker?
No, except for an all-in-one cooker: NF C 15-100 provides for one dedicated circuit for the hob and another for the oven.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Legrand, disjoncteur pour plaque à induction · Nexans, tableau des sections et calibres NF C 15-100.