Circuit breaker or residual current switch: what is the difference?

Three devices with similar names, three different roles in the distribution board. Understanding the difference helps you read a quote and know why a device "trips".

Published 16 November 2026 · 3 min read · SIGMA ICC, engineering consultancy

The circuit breaker protects cables and appliances against overloads and short circuits. The residual current switch protects people: it cuts the power as soon as it detects a leak to earth, for example when someone touches a live part. The residual current circuit breaker combines both functions in a single device. In a home distribution board, you generally find 30 mA residual current switches at the head of each row and miniature circuit breakers below them, one per circuit.

The three devices side by side

DeviceWhat it detectsWhat it protectsWhere it is found
Miniature circuit breaker (10, 16, 20, 32 A…)Overload, short circuitThe cables of one circuitOne per circuit
30 mA residual current switchEarth leakage currentPeopleAt the head of a group of circuits
Residual current circuit breakerBothCables and peopleMain incoming breaker, or a single circuit

The circuit breaker: protecting cables

Each cable can carry a maximum current: 1.5 mm² for 16 A, 2.5 mm² for 20 A, 6 mm² for 32 A, according to the NF C 15-100 benchmarks. If too many appliances are plugged in, the cable heats up; the circuit breaker trips before the insulation deteriorates. In the event of a short circuit, it trips within a few milliseconds. Its rating is therefore chosen according to the cable cross-section, never according to the appliance alone (see the cross-section / rating table).

The residual current switch: protecting people

It compares the current leaving through the phase with the current returning through the neutral. If more than 30 mA is missing, current is escaping elsewhere, through the earth or through a human body: it trips. It does not protect against overloads, hence the requirement for circuit breakers downstream. Its rating (25, 40 or 63 A) indicates the current it can carry, not its sensitivity. It comes in several types (AC, A, F) depending on the appliances protected: see which type of residual current device to choose.

The main incoming circuit breaker

At the head of the installation, after the meter, is the main circuit breaker. Depending on the distributor and the type of connection, it is a residual current type (with a sensitivity of a few hundred milliamps, for example 500 mA): it then provides overall protection and cuts the whole dwelling. It does not replace the 30 mA residual current devices, which alone protect people against direct contact.

What to do when it trips?

  • A miniature circuit breaker trips: overload or short circuit on that circuit. Unplug the appliances and reset; if it trips again with nothing connected, there is a wiring fault.
  • A residual current switch trips: current leakage on one of the circuits it protects, often a damp appliance or an outdoor socket. Switch off the circuit breakers one by one to find the faulty circuit.

The engineering firm sets out the protection scheme in the single-line diagram: number and type of residual current devices, circuit breaker ratings, discrimination between protection levels. This is the document the electrician follows and the inspection body checks.

Frequently asked questions

What is the difference between a circuit breaker and an RCD?

The circuit breaker trips in the event of an overload or short circuit to protect the cables; the residual current device trips as soon as a current leak exceeds its sensitivity (30 mA) to protect people.

Is a residual current switch enough without a circuit breaker?

No, the residual current switch does not protect against overloads: each circuit downstream must have its own circuit breaker suited to the cable cross-section.

What does 40 A mean on a 30 mA residual current switch?

40 A is the maximum current it can carry; 30 mA is its sensitivity, i.e. the leakage current at which it trips.