Condensate water must flow by gravity through a pipe with a continuous slope of at least about 1 cm per metre (1 to 2% according to common recommendations), then join the wastewater network via a trap. If a slope is impossible, a condensate lift pump is installed. Letting the water run down the façade or onto the pavement is the worst solution.
Where this water comes from
As it passes over the cold coil of the indoor unit, the air cools below its dew point and releases part of its water vapour, which trickles into a tray. The more humid the air and the more the unit runs, the more water it produces. Reversible air conditioning also produces water at the outdoor unit in heating mode, particularly during defrost cycles.
The rules for good drainage
- A continuous slope, with no back-fall or low point: standing water becomes a blockage and a source of odours.
- A sufficient diameter and a rigid pipe fixed at regular intervals, rather than a flexible hose that sags.
- A trap just before the connection to the wastewater stack, to prevent odours from rising back into the unit. It must remain accessible for maintenance.
- Pipe insulation where it passes through air-conditioned rooms, to prevent it from condensing on the outside itself.
- An authorised discharge point: the wastewater network is the normal solution. Discharging into rainwater drains or at the foot of the façade is not always permitted; check local rules and, in an apartment building, the co-ownership rules.
When is a lift pump needed
| Situation | Solution |
|---|---|
| Indoor unit high up, wastewater stack nearby and lower | Gravity drainage with a trap |
| No slope possible or drain located higher than the unit | Condensate lift pump |
| Ducted unit in a false ceiling with no drain point nearby | Pump with tray and overflow safety device |
A condensate pump must be chosen according to the flow rate and lift height, be accessible, and ideally be connected to a safety device that shuts off the air conditioner in the event of a fault. Its noise must be taken into account in bedrooms.
The most common faults
- Water drips from the indoor unit: blocked pipe, dirty tray, insufficient slope or unit not level.
- A sewer smell at start-up: trap missing or emptied by evaporation during the winter.
- A stain on the ceiling under a ducted unit: overflowing tray, failed pump or faulty connection.
- A blackened wall on the façade: condensate discharged into the open air, to be redone.
Cleaning the tray and the pipe is part of the annual air conditioning maintenance.
To be planned from the drawings stage
In new construction, condensate drains are planned at the same time as the plumbing: wastewater connection points near each indoor unit, accessible traps, openings reserved in partitions. The engineering firm draws them on the plumbing and air conditioning drawings, which avoids unsightly trunking and pumps added afterwards. See also the rules on wastewater drain slopes.
Frequently asked questions
What slope for AC condensate drainage?
A continuous slope of at least about 1 cm per metre, i.e. 1 to 2% according to common recommendations, with no back-fall or low point.
Is a trap needed on the condensate drain?
Yes, when it is connected to the wastewater network, an accessible trap placed before the connection prevents odours from rising back into the unit.
When should a condensate lift pump be installed?
When gravity drainage is impossible, for example if the drain is higher than the unit or too far away to obtain a sufficient slope.