Commercial kitchen extraction relies on four elements: a hood that amply covers all the cooking appliances, easily removable grease filters (baffle filters), a sealed, fire-resistant extraction duct that discharges air above the roofs, and a make-up air supply to replace the extracted air. The flow rate is calculated according to the appliances installed and their power, not according to the kitchen's floor area.
The hood and the filters
- The hood must extend beyond the cooking appliances to capture the fumes, which spread as they rise; the lower and more enveloping it is, the better it captures with a moderate flow rate.
- Baffle filters force the air to change direction several times: grease droplets settle and drain towards a gutter. They capture most of the large particles and act as a barrier against flames.
- Types of hood: traditional hood, induction hood (which blows part of the fresh air directly at the hood), filtering ceiling for large kitchens. Induction hoods or hoods with integrated make-up air make it possible, according to manufacturers, to reduce the extracted flow rate.
- The European standard NF EN 16282 governs the design of ventilation equipment for commercial kitchens; it serves as a technical reference, including in specifications in Morocco.
The extraction network
| Element | Good practice |
|---|---|
| Velocity in the duct | About 4 to 6 m/s, according to a reference manufacturer, to limit noise and deposits |
| Duct | Sealed sheet steel, access hatches for cleaning, fire resistance where it passes through rooms |
| Fan | Placed on the roof or outside the kitchen volume, accessible, suited to greasy, hot air |
| Discharge | At roof level, away from windows and fresh air intakes, to avoid odours and complaints from neighbours |
| Make-up air | Introduced without draughts on the cooks, ideally treated (filtered, tempered) |
The fire risk
Grease deposited in filters and ducts is a formidable fuel: a fryer fire can spread through the entire network up to the roof. French guides point out that filters must be cleaned every week and the entire installation checked at least once a year; the duct must be degreased regularly by a specialist company. In Morocco, fire safety in buildings open to the public falls under decree no. 2-14-499; the precise requirements for a restaurant or hotel kitchen (fire separation, automatic suppression under the hood, gas shut-off) are to be confirmed with the inspection body and the Civil Protection service. See our article on fire safety of public buildings.
Common mistakes
- A hood that is too small or too high, letting smoke fill the dining room.
- No make-up air: the kitchen is under negative pressure, doors slam, the draught of gas appliances is disrupted and the hood no longer captures.
- A discharge on the façade or into a small courtyard, a source of conflict with neighbours, common in riads converted into restaurants.
- Ducts without access hatches, impossible to clean.
- A noisy fan fixed to a lightweight structure, which transmits vibrations to the bedrooms.
What the engineering firm brings
The engineering firm inventories the cooking appliances, calculates the extraction and make-up air flow rates, chooses the type of hood, designs the network up to the discharge point, deals with noise and vibration, and incorporates fire safety and hygiene requirements. For a guesthouse or a riad, it also coordinates the routing of the ducts with the existing architecture (see air conditioning a riad).
Frequently asked questions
How often should commercial hood filters be cleaned?
Reference guides require the filters to be cleaned every week and the entire installation to be checked at least once a year, with regular degreasing of the ducts.
Why is make-up air needed in a commercial kitchen?
Because the extracted air must be replaced; without make-up air, the kitchen goes into negative pressure, the hood captures poorly and the operation of gas appliances is disrupted.
Where should the extracted air from a restaurant kitchen be discharged?
At roof level, away from windows and fresh air intakes, to avoid odours and complaints; discharge on the façade or into a small courtyard must be avoided.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Xpair, conception de la ventilation des cuisines professionnelles · Xpair, hotte traditionnelle, à induction, plafond filtrant · France Air, la norme NF EN 16282.