Under the Moroccan seismic code (RPS 2000, 2011 version), the smallest dimension of a reinforced concrete column must be at least 25 cm for ductility levels ND1 and ND2, and at least 30 cm for level ND3. A 20 × 20 cm column is therefore not compliant, whatever load it carries.
What the code sets
| Requirement | Value or principle |
|---|---|
| Smallest dimension (ND1, ND2) | 25 cm minimum |
| Smallest dimension (ND3) | 30 cm minimum |
| Slenderness | Limited: a column that is too tall relative to its width must be widened |
| Critical zones | Closer stirrups at the ends of the column, at the bottom and top |
| Transverse reinforcement | Minimum diameter of 6 mm, closed stirrups |
The ductility level (ND1 to ND3) depends on the seismic zone, the building class and the structural system adopted by the engineer; the engineer states it in the design calculations.
Reinforcement: to be calculated, not copied
The number and diameter of the longitudinal bars depend on the calculated forces (vertical loads and earthquake). The code sets minimum and maximum steel percentages, and closer stirrups in the critical zones, near the floors, where plastic hinges form during an earthquake. In these zones, stirrup spacing is limited to roughly the smallest of three values: 8 times the diameter of the longitudinal bars, a quarter of the smallest column dimension, and 15 cm. The exact spacing and the length of the critical zones are to be determined by the engineer.
Mistakes seen on site
- 20 cm columns to "save space" in the walls: not compliant with the RPS.
- Stirrups spaced 20 to 25 cm apart over the full height, with no tighter spacing at the ends.
- Unclosed stirrups or poorly hooked ones, which open up during an earthquake.
- Bar laps all at the same level, just above the floor, in the most heavily loaded zone.
- Short columns created by a spandrel or partial wall: they concentrate forces and fail first.
- Column-beam joints without stirrups, because they are difficult to reinforce.
Interior, corner or façade column
A corner or façade column does not carry the same load as a central column, but it undergoes more bending. Columns in the same row may therefore have different reinforcement. On a serious structural drawing, each column has a reference and specific reinforcement. To understand the regulatory context, read our article on RPS 2011.
The role of the engineering firm
The engineering firm calculates the forces in each column, sets its cross-section and reinforcement, and draws the stirrup details in the critical zones. Checking the reinforcement before pouring makes it possible to verify that these provisions are actually in place before it is too late.
Frequently asked questions
What is the minimum column size in Morocco?
RPS 2000 (2011 version) requires a smallest dimension of at least 25 cm for ductility levels ND1 and ND2, and 30 cm for level ND3.
Is a 20 × 20 cm column allowed?
No: it is below the 25 cm minimum dimension set by the Moroccan seismic code for reinforced concrete columns.
Why tighten the stirrups at the top and bottom of columns?
These are the critical zones where forces concentrate during an earthquake: closely spaced stirrups confine the concrete and stop the bars from buckling.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Ministère de l'Habitat, règlement parasismique RPS 2000 · Le Chantier, normes parasismiques RPS au Maroc.