NF C 15-100 limits voltage drop, measured from the origin of the installation to the appliance, to 3% for lighting and 5% for other uses. On a 230 V network, that is about 6.9 V and 11.5 V. Beyond that, motors overheat, lights dim and some electronic devices go into fault mode. As the distance increases, the cable cross-section must be increased.
The simplified formula
For a single-phase copper circuit, with a power factor close to 1:
- ΔU (in volts) = 2 × ρ × L × I / S
- ρ: resistivity of copper in service, taken as 0.0225 Ω·mm²/m;
- L: cable length in metres (one way, hence the factor of 2);
- I: current in amperes; S: cross-section in mm².
In balanced three-phase, the factor of 2 is replaced by 1.732 and the reference voltage is 400 V. For large cables and motors, the full calculation also takes reactance and cos φ into account.
Worked examples
| Case | Calculation | Result |
|---|---|---|
| 32 A hob, 15 m in 6 mm² | 2 × 0.0225 × 15 × 32 / 6 | 3.6 V, i.e. 1.6%: OK |
| 16 A garden shed, 60 m in 2.5 mm² | 2 × 0.0225 × 60 × 16 / 2.5 | 17.3 V, i.e. 7.5%: too much |
| Same shed in 6 mm² | 2 × 0.0225 × 60 × 16 / 6 | 7.2 V, i.e. 3.1%: OK |
| 32 A EV charger, 40 m in 6 mm² | 2 × 0.0225 × 40 × 32 / 6 | 9.6 V, i.e. 4.2%: borderline |
| Same charger in 10 mm² | 2 × 0.0225 × 40 × 32 / 10 | 5.8 V, i.e. 2.5%: OK |
Indicative maximum lengths
Maximum lengths from the board, in single-phase, calculated with the formula above at the current of the protective device rating, assuming no voltage drop upstream of the board:
| Circuit | Cross-section | Limit | Maximum length |
|---|---|---|---|
| 10 A lighting | 1.5 mm² | 3% | about 23 m |
| 16 A sockets | 2.5 mm² | 5% | about 40 m |
| 20 A sockets or dedicated circuit | 2.5 mm² | 5% | about 32 m |
| 32 A hob | 6 mm² | 5% | about 48 m |
These values are orders of magnitude. In reality, part of the voltage drop is already used up between the meter and the board, especially when the meter box is at the property boundary, far from the house. Design offices therefore keep a margin.
Risky situations in a villa
- The cable between the meter and the board: in housing estates around Marrakech, the meter box is often in the boundary wall, 30 or 50 m from the house. An undersized cable penalises every circuit.
- Outdoor areas: garden lighting, pool house, filtration room, motorised gate, well pump.
- Sub-boards for an upper floor or an outbuilding, supplied by a long cable.
- Heat: a cable laid in a conduit exposed to the sun or in an overheated roof carries less current; the cross-section is also checked against the installation conditions.
The role of the design office
The design office sizes each cable according to three criteria: heating (current-carrying capacity depending on installation method), short-circuit protection and voltage drop. It is almost always voltage drop that determines the cross-section of long runs. For the link between cable size and rating, see the cable size and circuit breaker rating table.
Frequently asked questions
What maximum voltage drop does the standard allow?
NF C 15-100 limits voltage drop to 3% for lighting and 5% for other uses, measured from the origin of the installation, i.e. about 6.9 V and 11.5 V at 230 V.
What cable size to supply a shed 60 m away?
For 16 A at 60 m in single-phase, 2.5 mm² gives about 7.5% voltage drop, which is too high; at least 4 mm² is needed, and preferably 6 mm² to keep a margin.
How do you calculate voltage drop?
In single-phase copper: ΔU = 2 × 0.0225 × length × current / cross-section. Then divide by 230 V to get the percentage.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Voltflow, chute de tension et règle des 3 % NF C 15-100.