Home / Advice / Electrical / Voltage drop

Voltage drop and cable length: calculation and rules to follow

The longer and thinner a cable, the more the voltage falls at the far end. In a villa with a garden, pool house or distant gate, it is often the length, not the circuit breaker rating, that determines the cable size.

Published 16 November 2026 · 5 min read · SIGMA ICC, engineering consultancy

NF C 15-100 limits voltage drop, measured from the origin of the installation to the appliance, to 3% for lighting and 5% for other uses. On a 230 V network, that is about 6.9 V and 11.5 V. Beyond that, motors overheat, lights dim and some electronic devices go into fault mode. As the distance increases, the cable cross-section must be increased.

The simplified formula

For a single-phase copper circuit, with a power factor close to 1:

  • ΔU (in volts) = 2 × ρ × L × I / S
  • ρ: resistivity of copper in service, taken as 0.0225 Ω·mm²/m;
  • L: cable length in metres (one way, hence the factor of 2);
  • I: current in amperes; S: cross-section in mm².

In balanced three-phase, the factor of 2 is replaced by 1.732 and the reference voltage is 400 V. For large cables and motors, the full calculation also takes reactance and cos φ into account.

Worked examples

CaseCalculationResult
32 A hob, 15 m in 6 mm²2 × 0.0225 × 15 × 32 / 63.6 V, i.e. 1.6%: OK
16 A garden shed, 60 m in 2.5 mm²2 × 0.0225 × 60 × 16 / 2.517.3 V, i.e. 7.5%: too much
Same shed in 6 mm²2 × 0.0225 × 60 × 16 / 67.2 V, i.e. 3.1%: OK
32 A EV charger, 40 m in 6 mm²2 × 0.0225 × 40 × 32 / 69.6 V, i.e. 4.2%: borderline
Same charger in 10 mm²2 × 0.0225 × 40 × 32 / 105.8 V, i.e. 2.5%: OK

Indicative maximum lengths

Maximum lengths from the board, in single-phase, calculated with the formula above at the current of the protective device rating, assuming no voltage drop upstream of the board:

CircuitCross-sectionLimitMaximum length
10 A lighting1.5 mm²3%about 23 m
16 A sockets2.5 mm²5%about 40 m
20 A sockets or dedicated circuit2.5 mm²5%about 32 m
32 A hob6 mm²5%about 48 m

These values are orders of magnitude. In reality, part of the voltage drop is already used up between the meter and the board, especially when the meter box is at the property boundary, far from the house. Design offices therefore keep a margin.

Risky situations in a villa

  • The cable between the meter and the board: in housing estates around Marrakech, the meter box is often in the boundary wall, 30 or 50 m from the house. An undersized cable penalises every circuit.
  • Outdoor areas: garden lighting, pool house, filtration room, motorised gate, well pump.
  • Sub-boards for an upper floor or an outbuilding, supplied by a long cable.
  • Heat: a cable laid in a conduit exposed to the sun or in an overheated roof carries less current; the cross-section is also checked against the installation conditions.

The role of the design office

The design office sizes each cable according to three criteria: heating (current-carrying capacity depending on installation method), short-circuit protection and voltage drop. It is almost always voltage drop that determines the cross-section of long runs. For the link between cable size and rating, see the cable size and circuit breaker rating table.

Frequently asked questions

What maximum voltage drop does the standard allow?

NF C 15-100 limits voltage drop to 3% for lighting and 5% for other uses, measured from the origin of the installation, i.e. about 6.9 V and 11.5 V at 230 V.

What cable size to supply a shed 60 m away?

For 16 A at 60 m in single-phase, 2.5 mm² gives about 7.5% voltage drop, which is too high; at least 4 mm² is needed, and preferably 6 mm² to keep a margin.

How do you calculate voltage drop?

In single-phase copper: ΔU = 2 × 0.0225 × length × current / cross-section. Then divide by 230 V to get the percentage.