In a domestic copper installation, the NF C 15-100 benchmarks are as follows: 1.5 mm² protected by a 16 A circuit breaker, 2.5 mm² by 20 A, 4 mm² by 25 A, 6 mm² by 32 A and 10 mm² by 40 A for certain high-power circuits. The principle is simple: the circuit breaker must trip before the cable heats up, so its rating must never exceed what the cross-section can carry.
The usual table (copper, dwelling)
| Cross-section | Maximum circuit breaker | Common uses |
|---|---|---|
| 1.5 mm² | 16 A (10 A or 16 A for lighting) | Lighting (8 points maximum), sockets (8 outlets maximum), roller shutters |
| 2.5 mm² | 20 A | Sockets (12 outlets maximum), oven, washing machine, dishwasher, tumble dryer, water heater, three-phase hob |
| 4 mm² | 25 A | Supply to a sub-distribution board, appliances of 4 to 5 kW |
| 6 mm² | 32 A | Single-phase hob or cooker, sub-distribution board |
| 10 mm² | 40 A | Large heating appliances, supply to a sub-distribution board |
These correspondences are those of the NF C 15-100 table reproduced by cable manufacturers. They apply to standard lengths and usual installation methods (embedded conduits). They do not replace a calculation when conditions differ from these assumptions.
When the table is no longer enough
- Long distances: on a sprawling villa, a pool house or a gate 60 m from the board, voltage drop may require a larger cross-section than in the table.
- High ambient temperature: a cable laid on a flat roof or in roof spaces that exceed 50 °C in summer in Marrakech carries less current than at 30 °C; correction factors are then applied.
- Grouped cables: several cables packed in the same conduit or cable tray heat up more; the cross-section must be corrected.
- Main supply and risers: the cable between the meter and the board, or the risers of a building, are always calculated according to the contracted power and the length.
Common mistakes
- Replacing a 16 A circuit breaker with a 20 A one because it "trips": if the cable is 1.5 mm², it is no longer protected.
- Mixing cross-sections on the same circuit: a 1.5 mm² section on a 20 A circuit becomes the weak link.
- Using cable of dubious quality: an actual cross-section smaller than the stated one invalidates the whole calculation. Insist on cable that complies with Moroccan standards and is inspected.
The role of the engineering firm
For a villa, a building or commercial premises, the engineering firm calculates each line: operating current, installation method, temperature, length, voltage drop and breaking capacity. The result appears in the calculation note and on the single-line diagram. See also how many sockets per circuit and the oven and hob cable.
Frequently asked questions
Which circuit breaker for 2.5 mm² cable?
A 2.5 mm² copper cable is protected by a circuit breaker of 20 A maximum according to the NF C 15-100 benchmarks.
What cable size for a 32 A circuit breaker?
A 32 A circuit breaker protects a 6 mm² copper cable, for example for a single-phase hob.
Can a 20 A circuit breaker be used on 1.5 mm² cable?
No, 1.5 mm² is protected by a 16 A circuit breaker at most; a 20 A one would let the cable overheat without tripping.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Nexans, tableau des sections et calibres NF C 15-100 · 123elec, quel disjoncteur selon le conducteur.