A dedicated circuit is a line running from the distribution board to supply a single high-power appliance. NF C 15-100 requires at least 4 dedicated circuits in a dwelling: one circuit for the cooker or hob (6 mm², 32 A circuit breaker in single-phase) and at least three circuits for appliances such as the washing machine, dishwasher, oven or tumble dryer, usually in 2.5 mm² protected by a 20 A circuit breaker.
The list of dedicated circuits
| Appliance | Usual cross-section | Usual protection |
|---|---|---|
| Hob or cooker (single-phase) | 6 mm² | 32 A circuit breaker |
| Hob (three-phase) | 2.5 mm² | 20 A circuit breaker |
| Oven, washing machine, dishwasher, tumble dryer | 2.5 mm² | 20 A circuit breaker |
| Single-phase electric water heater | 2.5 mm² | 20 A circuit breaker |
| Freezer | 2.5 mm² | 20 A circuit breaker (dedicated circuit recommended) |
| Air conditioner, heat pump, pool pump | Depending on power and manual | According to the manufacturer's instructions |
These values are the usual NF C 15-100 benchmarks (table of cross-sections and ratings reproduced by cable manufacturers). For powerful appliances or those far from the board, the cross-section is recalculated according to the length to limit voltage drop.
Why one line per appliance
- Avoid overloads: an oven (2 to 3.5 kW) and a washing machine heating water on the same line quickly exceed 16 A.
- Limit outages: a fault on the washing machine must not cut off the refrigerator or the lighting.
- Choose the right residual current device: the washing machine and the hob must be downstream of a 30 mA type A residual current switch, see types AC, A and F.
Air conditioning, a special case in Morocco
In Marrakech, where summer temperatures regularly exceed 40 °C, air conditioning is often the largest consumption item. Each outdoor unit, each ducted unit and each VRV system must have its own dedicated circuit, sized according to the current stated by the manufacturer, with an isolating device nearby for maintenance. "Inverter" air conditioners contain variable-speed electronics: equipment manufacturers recommend a type F residual current device for them (or type A depending on the appliance). The villa's other equipment follows the same logic: pool pump, booster pump, motorised gate, charging point.
Plan them at the design stage
Adding a dedicated circuit afterwards means running a new line and often cutting new wall chases. The engineering firm prepares the power balance, lists all appliances (including those that will be bought later), sets the cross-sections and ratings, and checks that the board keeps sufficient spare capacity. For the kitchen in particular, read our article on the cable and circuit breaker for the oven and hob.
Frequently asked questions
How many dedicated circuits does a house need?
NF C 15-100 requires at least 4: a 32 A circuit for the hob or cooker and three circuits for appliances such as the washing machine, dishwasher and oven.
Must an electric water heater have its own circuit?
Yes, the electric water heater is supplied by a dedicated circuit, commonly 2.5 mm² protected by a 20 A circuit breaker for a standard single-phase appliance.
Should an air conditioner be on a dedicated circuit?
Yes, each air conditioner or outdoor unit must have its own line, sized according to the current given by the manufacturer and protected by a suitable residual current device, often type F for inverter models.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Nexans, tableau des sections et calibres NF C 15-100 · Legrand, quel différentiel pour une climatisation · Legrand, que brancher sur un différentiel de type A.