Cable cross-section and circuit breaker rating: the reference table

The circuit breaker rating is chosen according to the cross-section of the cable it protects. Here is the usual table for domestic installations, and the cases where you need to go beyond a table.

Published 16 November 2026 · 3 min read · SIGMA ICC, engineering consultancy

In a domestic copper installation, the NF C 15-100 benchmarks are as follows: 1.5 mm² protected by a 16 A circuit breaker, 2.5 mm² by 20 A, 4 mm² by 25 A, 6 mm² by 32 A and 10 mm² by 40 A for certain high-power circuits. The principle is simple: the circuit breaker must trip before the cable heats up, so its rating must never exceed what the cross-section can carry.

The usual table (copper, dwelling)

Cross-sectionMaximum circuit breakerCommon uses
1.5 mm²16 A (10 A or 16 A for lighting)Lighting (8 points maximum), sockets (8 outlets maximum), roller shutters
2.5 mm²20 ASockets (12 outlets maximum), oven, washing machine, dishwasher, tumble dryer, water heater, three-phase hob
4 mm²25 ASupply to a sub-distribution board, appliances of 4 to 5 kW
6 mm²32 ASingle-phase hob or cooker, sub-distribution board
10 mm²40 ALarge heating appliances, supply to a sub-distribution board

These correspondences are those of the NF C 15-100 table reproduced by cable manufacturers. They apply to standard lengths and usual installation methods (embedded conduits). They do not replace a calculation when conditions differ from these assumptions.

When the table is no longer enough

  • Long distances: on a sprawling villa, a pool house or a gate 60 m from the board, voltage drop may require a larger cross-section than in the table.
  • High ambient temperature: a cable laid on a flat roof or in roof spaces that exceed 50 °C in summer in Marrakech carries less current than at 30 °C; correction factors are then applied.
  • Grouped cables: several cables packed in the same conduit or cable tray heat up more; the cross-section must be corrected.
  • Main supply and risers: the cable between the meter and the board, or the risers of a building, are always calculated according to the contracted power and the length.

Common mistakes

  1. Replacing a 16 A circuit breaker with a 20 A one because it "trips": if the cable is 1.5 mm², it is no longer protected.
  2. Mixing cross-sections on the same circuit: a 1.5 mm² section on a 20 A circuit becomes the weak link.
  3. Using cable of dubious quality: an actual cross-section smaller than the stated one invalidates the whole calculation. Insist on cable that complies with Moroccan standards and is inspected.

The role of the engineering firm

For a villa, a building or commercial premises, the engineering firm calculates each line: operating current, installation method, temperature, length, voltage drop and breaking capacity. The result appears in the calculation note and on the single-line diagram. See also how many sockets per circuit and the oven and hob cable.

Frequently asked questions

Which circuit breaker for 2.5 mm² cable?

A 2.5 mm² copper cable is protected by a circuit breaker of 20 A maximum according to the NF C 15-100 benchmarks.

What cable size for a 32 A circuit breaker?

A 32 A circuit breaker protects a 6 mm² copper cable, for example for a single-phase hob.

Can a 20 A circuit breaker be used on 1.5 mm² cable?

No, 1.5 mm² is protected by a 16 A circuit breaker at most; a 20 A one would let the cable overheat without tripping.

A project in the pipeline?

SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.

Sources : Nexans, tableau des sections et calibres NF C 15-100 · 123elec, quel disjoncteur selon le conducteur.