The distribution board must be placed inside the dwelling or in a directly accessible annex room, with its controls between 0.90 m and 1.80 m above the floor (board without a door), and must keep at least 20% free slots for future additions. Under NF C 15-100, it is integrated into a dwelling technical duct (GTL), a column that also houses the communications enclosure and the incoming networks: 600 mm wide in a dwelling of more than 35 m², 450 mm below that.
Key benchmarks
| Item | Usual benchmark (NF C 15-100) |
|---|---|
| Height of controls | Between 0.90 m and 1.80 m from the floor; with a door, between 0.50 m and 1.80 m |
| Spare capacity | At least 20% free slots in a detached house, with no empty row |
| GTL, dwelling of more than 35 m² | 600 mm wide, about 200 mm deep |
| GTL, dwelling of 35 m² or less | 450 mm wide, about 150 mm deep |
| Location | In the dwelling or a directly accessible annex room, generally near the entrance or the garage |
For a dwelling adapted to people with reduced mobility, the height range is lower (Legrand cites 0.75 m to 1.30 m for the isolating device). These values are those of the 2002 edition as amended; the 2024 edition must be checked for projects that apply it.
How many rows?
The number of rows follows from the number of circuits: each miniature circuit breaker generally takes up one module, each residual current switch two or four modules, and a standard row has 13 or 18 modules. For a villa of 200 to 300 m², with 25 to 40 circuits, 6 to 8 residual current devices, a surge protector and contactors, a 4-row board is commonly needed, or even a main board plus sub-distribution boards per floor or for the pool. Add 20% spare capacity and wiring space: a board that is too small quickly becomes impossible to extend.
Where to place it in a villa?
- Near the entrance or the garage, accessible without going through a bedroom, and not in a bathroom or above a sink.
- Away from heat: in Marrakech, a board in an unventilated, west-facing room can exceed 40 °C in summer, which makes the devices heat up and causes tripping.
- Close to the centre of gravity of the loads to limit cable length and voltage drop, particularly towards the kitchen and the air conditioning units.
- In a riad: provide a ventilated plant room and one sub-distribution board per floor rather than dozens of cables running through the old walls.
What the GTL contains
- The main incoming circuit breaker and the distribution board.
- The communications enclosure (telephone, fibre, RJ45, television).
- The incoming networks from the meter (Radeema, ONEE or another distributor).
- Socket outlets to power the internet box and the equipment in the enclosure.
The engineering firm draws the board on the single-line diagram, counts the modules and places the GTL on the architect's drawings from the design stage, to avoid squeezing it into a cupboard that is too narrow later on. See also the number of residual current devices and dedicated circuits.
Frequently asked questions
At what height should a distribution board be installed?
Under NF C 15-100, the controls of a board without a door are between 0.90 m and 1.80 m from the floor; with a door, the range is 0.50 m to 1.80 m.
How much spare capacity should a distribution board have?
At least 20% free slots in a detached house, without leaving any row completely empty, so that circuits can be added later.
How wide should a GTL be?
600 mm wide and about 200 mm deep for a dwelling of more than 35 m², 450 mm wide for a dwelling of 35 m² or less.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : IZI by EDF, à quelle hauteur installer un tableau électrique · Legrand, quelle hauteur pour un tableau électrique · Eduscol, fiche ETEL et GTL.