Under the NF C 15-100 rules (2002 edition as amended, still very widely applied), a 16 A socket-outlet circuit can supply a maximum of 8 outlets if it is wired in 1.5 mm² and protected by a 16 A circuit breaker, and a maximum of 12 outlets if it is wired in 2.5 mm² and protected by a 20 A circuit breaker. These limits prevent a single cable from being overloaded by too many appliances plugged in at the same time.
The table to remember
| Conductor cross-section (copper) | Protection | Maximum number of outlets |
|---|---|---|
| 1.5 mm² | 16 A circuit breaker | 8 |
| 2.5 mm² | 20 A circuit breaker | 12 |
| 2.5 mm² (kitchen worktop sockets) | 20 A circuit breaker | 6, on a circuit dedicated to the kitchen |
A fuse is not an alternative to the circuit breaker for the 1.5 mm² circuit: in new installations, protection is provided by a miniature circuit breaker. Like every circuit, the socket circuit is also placed downstream of a 30 mA residual current device.
How to count sockets
- One outlet = one socket: since the 2015 amendment, a double or triple socket block counts as 2 or 3 outlets. The old rules of counting per box no longer apply.
- Dedicated sockets do not count: the washing machine, oven, dishwasher or air conditioner have their own circuit (see dedicated circuits).
- Switched sockets (turned on by a light switch) count as sockets if they are on the socket circuit.
What this means in a villa
A 200 m² villa in Marrakech easily has 40 to 60 socket outlets. With 2.5 mm² / 20 A circuits, you therefore need at least 4 to 5 socket circuits, not counting the kitchen circuits and the dedicated circuits. In practice, the engineering firm groups the sockets by zone (living room, bedrooms, outdoors, office) so that a fault does not cut power to the whole house, and to balance the loads between the residual current devices, or even between the phases in a three-phase supply.
Two tips from the field: avoid putting the sockets of an office with computer equipment on the same circuit as those of a room where a portable heater or an iron is plugged in during winter, and provide a dedicated circuit for outdoor sockets (garden, terrace, pool), which are more exposed to moisture.
What about the Moroccan standard?
In Morocco, standards NM 06.1.100 to 06.1.106 published by IMANOR govern low-voltage installations; NM 06.1.100 was approved in 2025. In specifications (CPS) and design studies, NF C 15-100 remains the most cited technical reference. Its 2024 edition replaced the 2002 edition and reorganises the standard into several parts: the engineering firm checks which edition applies to your contract and what the inspection body requires.
The role of the engineering firm
An electrical engineering firm draws up the single-line diagram, the number of circuits, the cross-sections and the ratings, taking into account cable lengths (voltage drop) and the power actually contracted with Radeema or ONEE. This file is what allows you to compare electricians' quotes on a clear basis. For the general framework, see also our article on the NF C 15-100 standard in Morocco.
Frequently asked questions
How many sockets on a 16 A circuit breaker?
Under NF C 15-100, a 1.5 mm² circuit protected by a 16 A circuit breaker can supply a maximum of 8 socket outlets.
How many sockets on a 20 A circuit breaker?
A 2.5 mm² circuit protected by a 20 A circuit breaker can supply up to 12 outlets, except in the kitchen where the worktop circuit is limited to 6 outlets.
Does a double socket count as one or two sockets?
It counts as two: since the 2015 amendment to NF C 15-100, each outlet of a multiple block is counted separately.
A project in the pipeline?
SIGMA ICC designs reinforced concrete, electrical, plumbing and HVAC systems and supervises sites for villas, riads, hotels and shops.
Sources : Legrand, combien de prises sur un disjoncteur 16 A · IZI by EDF, nombre de prises par disjoncteur · IMANOR, catalogue des normes marocaines.